NAME
mge-shut - Driver for MGE UPS serial SHUT Protocol UPS equipment
NOTE
This man page only documents the hardware-specific features of the
mge-shut driver. For information about the core driver, see
nutupsdrv(8).
SUPPORTED HARDWARE
mge-shut support all recent MGE UPS models which use the SHUT (Serial HID
UPS Transfer) protocol at 2400 bps. Supported models are:
Pulsar Ellipse S,
Pulsar Ellipse Premium S,
Pulsar EXtreme C,
Pulsar Esprit,
Pulsar / Comet EXtreme,
Galaxy 3000 / PW (with RS232 HID COM ports card, ref 66066).
Older models, such as Pulsar ESV+, Pulsar EX and Pulsar ES+, use the U-Talk
protocol and should use the mge-utalk driver.
EXTRA ARGUMENTS
This driver supports the following optional settings in the
ups.conf(5):
- lowbatt=num
-
Set the low battery warning threshold at which shutdown is initiated by
upsmon(8).
The factory default value is 30 (in percentage), and only be settable
depending on the exact model.
- offdelay=num
-
Set the timer before the UPS is turned off after the kill power command is
sent (via the -k switch).
The default value is 20 (in seconds), and MUST BE LOWER than ondelay.
- ondelay=num
-
Set the timer for the UPS to switch on in case the power returns after the
kill power command had been sent but before the actual switch off. This
ensures the machines connected to the UPS are, in all cases, rebooted after
a power failure.
The default value is 3 (in 10 seconds units, which means 30 seconds),
and MUST BE GREATER than offdelay.
- notification=num
-
Set notification type to 1 (no), 2 (light) or 3 (yes).
The default value is 3 (yes) because of some early Ellipse models which
need it.
KNOWN ISSUES
Pulsar Ellipse S: Repetitive stale status - Loss of communication
Several users have reported "data stale" errors with Pulsar Ellipse
equipment. This lasts around 10 seconds and happens once every few hours.
This is due to the fact that the SHUT protocol is verbose, and the driver
sometimes does not handle all of it during the usual polling interval in
upsd. To solve this problem, change the value of MAXAGE to 25 in
upsd.conf. Also add "notification=3" in ups.conf (thanks to Julien
Lesaint and Fabien).
AUTHOR
Arnaud Quette <
arnaud.quette@free.fr> or <
arnaud.quette@mgeups.com>
Philippe Marzouk <philm@users.sourceforge.net>
SEE ALSO
The core driver:
nutupsdrv(8)
Internet resources:
The NUT (Network UPS Tools) home page:
http://www.networkupstools.org/
MGE UPS SYSTEMS SHUT protocol information:
http://random.networkupstools.org/protocols/mge/
Index
- NAME
-
- NOTE
-
- SUPPORTED HARDWARE
-
- EXTRA ARGUMENTS
-
- KNOWN ISSUES
-
- Pulsar Ellipse S: Repetitive stale status - Loss of communication
-
- AUTHOR
-
- SEE ALSO
-
- The core driver:
-
- Internet resources:
-